Battery C-Rate Calculator
Convert between battery capacity, C-rate and charge or discharge current in one step, and see how long the pack lasts at that rate. Solve for current, C-rate or the capacity you need, check the result against the safe continuous limit for LiFePO4, Li-ion, LiPo, NiMH, LTO and lead-acid, and read off power, energy and a full C-rate ladder from 0.05C to 20C.
Trình chặn quảng cáo đang ngăn chúng tôi hiển thị quảng cáo
MiniWebtool miễn phí nhờ quảng cáo. Nếu công cụ này hữu ích với bạn, hãy ủng hộ chúng tôi bằng cách nâng cấp để duyệt không quảng cáo và có nhiều lượt dùng mỗi ngày hơn, hoặc cho phép MiniWebtool.com rồi tải lại.
- Cho phép quảng cáo cho MiniWebtool.com, rồi tải lại
- Hoặc nâng cấp để không quảng cáo và có giới hạn hằng ngày cao hơn
Giới thiệu về Battery C-Rate Calculator
The Battery C-Rate Calculator converts between capacity, C-rate and charge or discharge current in a single step. Enter any two of the three and the calculator returns the third, together with the time the pack takes to empty or fill at that rate, the power and energy involved, and a check of whether the rate is safe for your cell chemistry.
What Is a Battery C-Rate?
The C-rate expresses current as a multiple of a battery's rated capacity, so a single number describes the same relative stress on a 2 Ah phone cell and a 400 Ah storage bank. 1C is by definition the current that would move the entire rated capacity in exactly one hour. On a 100 Ah battery that is 100 A; on a 3,000 mAh 18650 it is 3 A. Halving the C-rate halves the current and doubles the time, and doubling it does the opposite.
Because the number is relative, datasheets can state one safe limit — "1C continuous discharge" — that applies to every size in the range. That is why the C-rate, not the raw amperage, is the figure to check before you connect a load or a charger.
Battery C-Rate Formulas
Three quantities are linked by one relationship, so knowing two always gives the third.
If your capacity is given in milliamp-hours, either divide by 1,000 to get amp-hours or keep everything in milli-units and read the current in milliamps — the ratio is what matters, not the prefix.
C-Rate to Time Reference Table
| C-rate | Ideal time | Current on 100 Ah | Current on 3,000 mAh | Typical use |
|---|---|---|---|---|
| 0.05C | 20 h | 5 A | 150 mA | Lead-acid rating standard |
| 0.1C | 10 h | 10 A | 300 mA | Overnight solar storage |
| 0.2C | 5 h | 20 A | 600 mA | Deep-cycle house battery |
| 0.5C | 2 h | 50 A | 1.5 A | Standard lithium charging |
| 1C | 1 h | 100 A | 3 A | LiFePO4 continuous limit |
| 2C | 30 min | 200 A | 6 A | Power tools, e-bikes |
| 5C | 12 min | 500 A | 15 A | High-drain cells, LTO |
| 10C | 6 min | 1,000 A | 30 A | Drones, RC models |
| 20C | 3 min | 2,000 A | 60 A | RC racing burst draw |
Typical Safe C-Rates by Chemistry
These are conservative, widely published figures for continuous operation. Individual cells vary enormously between energy grades and power grades, so the datasheet for your exact cell always wins.
| Chemistry | Nominal V | Continuous discharge | Continuous charge |
|---|---|---|---|
| LiFePO4 (LFP) | 3.2 V | 1C | 0.5C |
| Li-ion NMC / 18650 | 3.6 V | 1–2C | 0.5C |
| LiPo (RC / high-drain) | 3.7 V | 20C and above | 1C |
| Lead-acid (AGM / flooded) | 12 V pack | 0.2C | 0.2C |
| NiMH | 1.2 V | 1C | 0.5C |
| LTO (lithium titanate) | 2.4 V | 10C | 5C |
Why Real Runtime Is Shorter Than 1 ÷ C-Rate
Higher current drops more voltage across the internal resistance, so the pack reaches its low-voltage cut-off before it is truly empty.
Losses rise with the square of current. A hot pack both wastes energy and ages faster at the same C-rate.
On lead-acid the chemistry itself cannot keep up at high current, so delivered amp-hours fall well below the rating.
Most packs are only cycled to 80% or 50% depth to preserve life, which cuts usable runtime by the same fraction.
Cold cells have higher internal resistance. Capacity at 0 °C can be 20–30% below the room-temperature rating.
A pack at 80% state of health delivers 80% of the amp-hours, so an old battery hits your C-rate limit sooner.
Charging: Why 1C Does Not Mean One Hour
Lithium chargers use a CC-CV profile. During the constant-current phase the charger holds your chosen C-rate until the cell reaches its maximum voltage, which happens at roughly 80% state of charge. It then holds that voltage while the current tapers away, and this taper adds time without adding much capacity. In practice a 1C charge reaches full in about 1.2 to 1.4 hours, and a 0.5C charge in a little over two. This calculator reports both the constant-current phase and a realistic total.
The Peukert Effect on Lead-Acid
Lead-acid capacity is quoted at the 20-hour rate — a 100 Ah battery means 5 A for 20 hours, which is only 0.05C. Draw it faster and you get fewer amp-hours out. The Peukert equation models this:
where \( H \) is the rating time (20 h), \( C \) the rated capacity, \( I \) the discharge current and \( n \) the Peukert exponent, typically 1.1–1.3 for lead-acid. This calculator uses \( n = 1.15 \), a representative AGM value. Lithium chemistries have an exponent close to 1.0, which is why they are treated as ideal here.
How to Use This Calculator
- Pick charge or discharge: the safe limits differ, so the verdict changes with the direction.
- Pick what to solve for: Current, C-Rate or Capacity. The chosen field is greyed out and the other two become your inputs.
- Enter the pack details: capacity in Ah or mAh, the known C-rate or current, and the cell chemistry. Add the nominal voltage if you want power and energy figures.
- Click Calculate: read the answer, the time at that rate, the safety gauge against the chemistry limit and the full C-rate ladder.
Worked Example
A 12 V, 100 Ah LiFePO4 battery powering a 0.5C load: the current is \( 0.5 \times 100 = 50\,\text{A} \), the ideal runtime is \( 1 / 0.5 = 2 \) hours, and the power drawn is \( 12 \times 50 = 600\,\text{W} \) from 1,200 Wh of stored energy. Since LiFePO4 is normally rated for 1C continuous, 0.5C sits comfortably at half the limit — a gentle, long-life operating point.
Frequently Asked Questions
What does C-rate mean on a battery?
C-rate expresses current as a multiple of the battery's rated capacity. 1C is the current that would empty the rated capacity in exactly one hour, so a 100 Ah battery at 1C draws 100 A. 0.5C is half that current for twice the time, and 2C is double the current for half the time.
How do I calculate current from C-rate?
Multiply the C-rate by the capacity in amp-hours: Current (A) = C-rate × Capacity (Ah). A 5 Ah pack at 2C draws 10 A. If your capacity is in mAh, divide it by 1,000 first, or work in mAh and read the answer in mA.
How long does a battery last at a given C-rate?
In theory the time is 1 divided by the C-rate, in hours: 0.5C lasts 2 hours, 1C lasts 1 hour, 2C lasts 30 minutes. Real runtime is shorter because of the cut-off voltage, temperature and, on lead-acid, the Peukert effect.
What is a safe C-rate for LiFePO4?
Most LiFePO4 cells are rated for about 1C continuous discharge and 0.5C charge, with short bursts to 2C or 3C. Large prismatic storage cells are often limited to 0.5C. Always confirm against your cell's datasheet, because ratings vary widely between grades.
Does charging at 1C really take one hour?
No. A CC-CV charger only holds the set current to roughly 80% state of charge and then tapers at constant voltage, so a 1C charge typically takes around 1.2 to 1.4 hours to reach full. The constant-current phase is the fast part; the taper adds the rest.
Why does a lead-acid battery deliver less capacity at high C-rate?
Lead-acid capacity is quoted at the 20-hour rate, roughly 0.05C. At higher currents the chemical reaction cannot keep up with demand, so the delivered amp-hours drop. The Peukert equation models this: a 100 Ah battery discharged at 0.2C may only deliver around 80 Ah.
Is a higher C-rating always better?
Not necessarily. A high C-rating means the cell can move current quickly, but high-rate cells usually trade away energy density, and running any cell near its limit produces heat and shortens cycle life. Sizing the pack so your load sits well below the rating usually gives the longest service.
What is the difference between continuous and burst C-rate?
The continuous rating is what the cell can sustain until empty without exceeding its temperature limit. The burst or peak rating applies for a few seconds, typically during acceleration or motor start-up. RC LiPo packs are marketed with burst figures, which is why a "50C" pack should not be run continuously at 50C.
Additional Resources
Tham khảo nội dung, trang hoặc công cụ này như sau:
"Battery C-Rate Calculator" tại https://MiniWebtool.com/vi/may-tinh-c-rate-pin/ từ MiniWebtool, https://MiniWebtool.com/
by miniwebtool team. Updated: August 20, 2026
Công cụ Điện tử:
- Máy tính tuổi thọ pin
- Máy tính mã màu điện trở
- Máy tính định luật Ohm
- Máy tính sụt áp
- Máy tính độ rộng đường mạch PCB Nổi bật
- Máy Tính Tiết Diện Dây Dẫn Mới
- Máy Tính Điện Trở LED Mới
- Máy Tính Bộ Chia Điện Áp Mới
- Máy tính Điện trở Song song Mới
- Máy Tính Tụ Điện Mới
- Máy tính Timer 555 Mới
- Máy tính Biến áp Mới
- RC Time Constant Calculator Mới
- Máy tính Hệ số Công suất Mới
- Máy tính Decibel (dB) Mới
- Máy tính Trở kháng Mới
- Máy tính Tần số Cộng hưởng Mới
- Trình Mô Phỏng Cổng Logic Mới
- Máy Tính Điện Trở Nối Tiếp Mới
- Máy Tính Watt Sang Ampe Mới
- Máy Tính Ampe Sang Watt Mới
- Máy Tính kVA Mới
- Máy Tính Công Suất 3 Pha Mới
- Công Cụ Chuyển Đổi mAh Sang Wh Mới
- Máy Tính Công Suất Máy Phát Điện Mới
- Máy Chuyển Đổi Lumen Sang Watt Mới
- Máy Tính Lux Sang Lumen Mới
- Máy Tính Chiếu Sáng Phòng Mới
- Máy Tính Cảm Kháng Mới
- Máy Tính Tụ Điện Nối Tiếp và Song Song Mới
- Máy Tính Độ Lấp Đầy Ống Lót Dây Mới
- Máy Tính Chiều Dài Anten Mới