Capacitor Bank Sizing Calculator
Find the capacitor bank kVAR needed to correct your power factor to a target value. Enter kW, kVA, or measured volts and amps, and get the required kVAR, a matching standard capacitor bank built from real off-the-shelf steps, the per-phase capacitance in microfarads for both delta and wye connections, capacitor current with NEC 460.8 conductor and fuse sizing, released transformer capacity, and an animated power triangle showing the correction.
你的廣告攔截器讓我們無法顯示廣告
MiniWebtool 依靠廣告收入免費提供服務。如果這個工具幫到了你,歡迎升級以獲得無廣告瀏覽和更多每日使用次數,或將 MiniWebtool.com 加入白名單後重新整理。
- 允許 MiniWebtool.com 顯示廣告,然後重新整理
- 或升級取得無廣告瀏覽和更高每日額度
Capacitor Bank Sizing Calculator
The Capacitor Bank Sizing Calculator tells you exactly how many kVAR of power factor correction capacitors a load needs to move from its present power factor to a target such as 0.95. Enter the load as kW, as kVA, or as a clamp-meter reading in volts and amps, and the calculator returns the required kVAR, a bank you can actually buy built from standard capacitor ratings, the capacitance in microfarads for both delta and wye connections, the capacitor current with conductor and fuse sizing, and the transformer capacity the correction releases.
What is a capacitor bank and why size it?
Motors, transformers, welders and fluorescent ballasts are inductive: they draw a magnetising current that lags the voltage. That current does no useful work, but it still flows through every cable, breaker and transformer between the load and the utility. A capacitor bank installed near the load supplies that magnetising current locally, so the supply only has to deliver the real power. The result is a higher power factor, lower line current, less voltage drop, fewer losses, and — usually the reason the project gets funded — no more power factor penalty on the electricity bill.
Sizing matters in both directions. Too little kVAR and the penalty stays. Too much and the system overcorrects into a leading power factor at light load, which raises voltage, can upset generators and standby sets, and is penalised by many tariffs exactly like a lagging power factor.
Capacitor bank sizing formula
The whole calculation rests on one idea: capacitors change the reactive power \(Q\) and leave the real power \(P\) alone. The required kVAR is simply the difference between the reactive power you have and the reactive power you want.
Where \(PF_1\) is the present power factor, \(PF_2\) the target, \(f\) the supply frequency in hertz, and \(V_{LL}\) the line-to-line voltage. The bracketed term is the familiar kVAR multiplier found in correction tables — it is what the table below lists.
Worked example
A 480 V three-phase plant draws 100 kW at a power factor of 0.75 and the utility wants 0.95. \(\tan(\cos^{-1}0.75) = 0.8819\) and \(\tan(\cos^{-1}0.95) = 0.3287\), so the multiplier is 0.5532 and the bank needs \(100 \times 0.5532 = 55.3\) kVAR. The nearest buildable bank is 60 kVAR (a 50 plus a 10), the apparent power falls from 133.3 kVA to 105.3 kVA, and the line current drops from 160 A to 127 A — 28 kVA of transformer capacity handed back without touching the transformer.
kVAR multiplier table
Multiply your load in kW by the factor where your present power factor meets your target.
| Present PF | Target 0.90 | Target 0.95 | Target 0.98 | Target 1.00 |
|---|---|---|---|---|
| 0.60 | 0.849 | 1.005 | 1.130 | 1.333 |
| 0.65 | 0.685 | 0.840 | 0.966 | 1.169 |
| 0.70 | 0.536 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.398 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.266 | 0.421 | 0.547 | 0.750 |
| 0.85 | 0.135 | 0.291 | 0.417 | 0.620 |
| 0.90 | — | 0.156 | 0.281 | 0.484 |
| 0.92 | — | 0.097 | 0.223 | 0.426 |
| 0.95 | — | — | 0.126 | 0.329 |
Notice how the last column grows. Going from 0.95 to 1.00 on a 100 kW load costs another 32.9 kVAR — about the same again as correcting 0.90 to 0.95 twice over. That is why almost nobody corrects to unity.
Delta or wye — which connection?
Each cell sits across the full line-to-line voltage, so it produces three times the reactive power per microfarad. Needs the least capacitance and is the standard choice for low-voltage banks below 600 V. Every cell must be rated for the full line voltage.
Each cell sees only \(V/\sqrt{3}\), so it needs three times the capacitance for the same kVAR but a lower voltage rating. Common at medium and high voltage, usually ungrounded, with the neutral used for unbalance and blown-fuse detection.
Fixed, switched or automatic?
Always connected. Correct for a base load that never goes away — a transformer's magnetising kVAR, or a motor that runs continuously. Size it to the minimum load so it can never overcorrect.
Several steps switched in and out by a power factor controller. The right answer whenever load varies through the shift or the total exceeds roughly 100 kVAR. Aim for 4 to 8 steps so correction tracks the load closely.
A series reactor tunes the bank below the 5th harmonic. Required wherever variable-speed drives, rectifiers or UPS systems make up a large share of the load, otherwise the capacitors and the harmonic source can resonate.
How to use this calculator
- Pick Three-Phase or Single-Phase and the supply frequency.
- Choose how you know the load: real power in kW, apparent power in kVA, or a measured current in amps at the system voltage.
- Enter the Current Power Factor — the value on the utility bill or the power meter. Both 0.78 and 78 are accepted.
- Enter the Target Power Factor. Use the threshold in your tariff, typically 0.90 or 0.95.
- Press Calculate kVAR, then use the target slider in the results to see how the bank size responds before you commit to a rating.
What power factor correction actually saves
- Penalty removal. Tariffs charge either a power factor penalty below a threshold or a demand charge on kVA. Both disappear once the measured power factor sits above the target.
- Released capacity. Apparent power falls from \(P/PF_1\) to \(P/PF_2\). That freed kVA is real headroom on the transformer, switchgear and feeders — often enough to add load without an upgrade.
- Lower losses. Line current falls in the ratio \(PF_1/PF_2\), and resistive losses fall with the square of that ratio. Correcting 0.75 to 0.95 cuts current by about 21% and \(I^2R\) losses by about 38%.
- Better voltage. Less current means less voltage drop along long feeders, which helps motors start and run cooler.
Common mistakes when sizing a capacitor bank
- Sizing from peak kW but running at part load. A fixed bank sized for the busiest hour will overcorrect at night. Size fixed banks to the minimum load and switch the rest.
- Ignoring harmonics. Capacitors are a low-impedance path for harmonic current. With significant drive or rectifier load, specify a detuned bank instead of plain capacitors.
- Bolting too much kVAR onto a motor. Exceeding the manufacturer's maximum kVAR for terminal correction can self-excite the motor on coast-down and produce damaging overvoltage.
- Undersized conductors and protection. NEC 460.8 wants at least 135% of rated capacitor current in the conductor; protection is normally set at 135–165%.
- Forgetting discharge time. Capacitors store energy after the supply is opened. Codes require the residual voltage to fall to a safe level within a set time — never re-energise or work on a bank before the discharge resistors have done their job.
Frequently asked questions
How do I calculate the kVAR of a capacitor bank?
Multiply the real power in kW by the difference of the tangents of the two power factor angles: \(Q_C = kW \times (\tan\phi_1 - \tan\phi_2)\). A 100 kW load at 0.75 corrected to 0.95 needs \(100 \times (0.8819 - 0.3287) = 55.3\) kVAR.
What target power factor should I choose?
Match the threshold in your tariff. 0.95 is the common commercial target; 0.98 is worth it where the utility bills on kVA demand. Correcting to 1.00 is rarely economic and increases the risk of a leading power factor at light load.
How many microfarads is 1 kVAR?
It depends entirely on voltage and frequency, because \(C = Q / (2\pi f V^2)\). At 480 V and 60 Hz, one kVAR in a delta bank is roughly 3.8 µF per phase; at 240 V and 60 Hz the same kVAR needs about 15 µF, four times as much, because capacitance scales with the inverse square of voltage.
Can a capacitor bank be too large?
Yes. Overcorrection pushes the power factor leading, raises system voltage, can trip generator reverse-VAR protection and is often penalised by the utility. If the load varies, use an automatic bank with several switched steps rather than one large fixed block.
Does correcting power factor reduce my kWh consumption?
Only slightly. Capacitors do not reduce the real energy the load consumes; the meter's kWh register barely moves. The savings come from the removed penalty or kVA demand charge, the released capacity, and a modest cut in resistive losses in your own cables.
Where should the capacitors be installed?
The closer to the inductive load, the more of the distribution system is relieved. Individual correction at the motor gives the biggest loss reduction; group correction at a motor control centre is a good compromise; bulk correction at the main switchboard fixes the utility bill but leaves the internal cables carrying the same reactive current.
Disclaimer: this calculator provides guideline figures for planning and study purposes. Final capacitor bank design, harmonic analysis, protection settings and conductor sizing must be reviewed by a qualified electrical engineer against the applicable local code and the equipment manufacturer's data.
引用此內容、頁面或工具為:
"Capacitor Bank Sizing Calculator" 於 https://MiniWebtool.com/zh-tw/電容補償櫃容量計算機/,來自 MiniWebtool,https://MiniWebtool.com/
by miniwebtool team. Updated: 2026-08-19
電子工具:
- 電池續航計算機
- 電阻色環計算機
- 歐姆定律計算機 精選
- 電壓降計算機
- PCB走線寬度計算機
- 線規計算機 新
- LED電阻計算機 新
- 分壓器計算機 新
- 並聯電阻計算機 新
- 電容器計算機 新
- 555定時器計算機 新
- 變壓器計算機 新
- RC時間常數計算機 新
- 功率因數計算機 新
- 分貝 (dB) 計算機 新
- 阻抗計算機 新
- 諧振頻率計算機 新
- 邏輯閘模擬器 新
- 串聯電阻計算機 新
- 瓦特轉安培計算機 新
- 安培轉瓦特計算機 新
- kVA計算機 新
- 三相功率計算機 新
- mah到wh轉換器 新
- 發電機功率計算機 新
- 流明轉瓦特轉換器 新
- 勒克斯轉流明計算機 新
- 房間照明計算機 新
- 感抗計算機 新
- 串聯並聯電容計算機 新
- 電線管填充率計算機 新
- 天線長度計算機 新