Wire Resistance Calculator
Calculate the electrical resistance of a wire from its length, AWG gauge (or area/diameter), conductor material and operating temperature. The tool applies the temperature coefficient to the resistivity, supports one-way or round-trip runs and parallel conductors, and adds the AC skin-effect resistance at any frequency, voltage drop and I²R power loss, a wire cross-section diagram, a resistance-vs-temperature chart and a full step-by-step breakdown.
Longer wire ⇒ more resistance · thicker wire ⇒ less resistance · hotter wire ⇒ more resistance
Votre bloqueur de publicités nous empêche d’afficher des annonces
MiniWebtool reste gratuit grâce aux annonces. Si cet outil vous a aidé, soutenez-nous en passant à une navigation sans publicité avec plus d’utilisations quotidiennes, ou autorisez MiniWebtool.com puis rechargez.
- Autorisez les annonces pour MiniWebtool.com, puis rechargez
- Ou passez à une offre sans publicité avec des limites quotidiennes plus élevées
Wire Resistance Calculator
The Wire Resistance Calculator works out the electrical resistance of a conductor from its length, gauge (AWG, area or diameter), material and operating temperature. It applies the temperature coefficient to the resistivity, handles round-trip runs and parallel conductors, and — unlike most resistance calculators — also gives you the AC resistance with skin effect, the resulting voltage drop and I²R power loss, and a side-by-side comparison with the neighbouring wire gauges.
Wire Resistance Formula
The resistance of any uniform conductor comes from three things: how resistive the material is, how long the current path is, and how much cross-section the current has to flow through.
Here \( \rho_{20} \) is the resistivity at 20 °C in Ω·m, \( \alpha \) is the temperature coefficient of resistance per °C, \( T \) is the operating temperature in °C, \( L \) is the total conductor length in metres (double the run length for an out-and-back circuit), \( A \) is the cross-sectional area in m², and \( n \) is the number of conductors in parallel.
Resistivity and Temperature Coefficient of Common Conductors
All values are at 20 °C. Resistivity is given both in Ω·m and in the practical unit Ω·mm²/m, which is simply the resistance of a 1 metre length with a 1 mm² cross-section.
| Material | ρ₂₀ (Ω·m) | ρ₂₀ (Ω·mm²/m) | α (per °C) | Density (g/cm³) |
|---|---|---|---|---|
| Silver | 1.59 × 10⁻⁸ | 0.0159 | 0.0038 | 10.49 |
| Copper (annealed) | 1.724 × 10⁻⁸ | 0.01724 | 0.00393 | 8.96 |
| Copper (hard-drawn) | 1.77 × 10⁻⁸ | 0.0177 | 0.00382 | 8.94 |
| Gold | 2.44 × 10⁻⁸ | 0.0244 | 0.0034 | 19.30 |
| Aluminum | 2.65 × 10⁻⁸ | 0.0265 | 0.00403 | 2.70 |
| Tungsten | 5.60 × 10⁻⁸ | 0.0560 | 0.0045 | 19.25 |
| Zinc | 5.90 × 10⁻⁸ | 0.0590 | 0.0037 | 7.14 |
| Nickel | 6.99 × 10⁻⁸ | 0.0699 | 0.0060 | 8.91 |
| Brass | 7.00 × 10⁻⁸ | 0.0700 | 0.0015 | 8.53 |
| Iron (pure) | 9.71 × 10⁻⁸ | 0.0971 | 0.0050 | 7.87 |
| Platinum | 1.06 × 10⁻⁷ | 0.106 | 0.00392 | 21.45 |
| Tin | 1.09 × 10⁻⁷ | 0.109 | 0.0045 | 7.31 |
| Steel (carbon) | 1.43 × 10⁻⁷ | 0.143 | 0.0030 | 7.85 |
| Constantan | 4.90 × 10⁻⁷ | 0.490 | 0.00002 | 8.90 |
| Manganin | 4.82 × 10⁻⁷ | 0.482 | 0.000002 | 8.40 |
| Nichrome 80/20 | 1.10 × 10⁻⁶ | 1.10 | 0.0004 | 8.40 |
AWG Wire Size Chart — Copper Resistance per 1000 ft and per km
American Wire Gauge is a geometric series: the diameter of gauge n is \( d = 0.127 \times 92^{(36-n)/39} \) mm. Every 3 gauges the area halves and the resistance doubles; every 6 gauges the diameter halves. Resistance figures below are for solid annealed copper at 20 °C.
| AWG | Diameter (mm) | Area (mm²) | Ω / 1000 ft | Ω / km |
|---|---|---|---|---|
| 4/0 (0000) | 11.684 | 107.2 | 0.0490 | 0.161 |
| 3/0 (000) | 10.405 | 85.0 | 0.0618 | 0.203 |
| 2/0 (00) | 9.266 | 67.4 | 0.0779 | 0.256 |
| 1/0 (0) | 8.251 | 53.5 | 0.0983 | 0.322 |
| 2 AWG | 6.544 | 33.6 | 0.156 | 0.513 |
| 4 AWG | 5.189 | 21.2 | 0.248 | 0.815 |
| 6 AWG | 4.115 | 13.3 | 0.395 | 1.30 |
| 8 AWG | 3.264 | 8.37 | 0.628 | 2.06 |
| 10 AWG | 2.588 | 5.26 | 0.999 | 3.28 |
| 12 AWG | 2.053 | 3.31 | 1.588 | 5.21 |
| 14 AWG | 1.628 | 2.08 | 2.525 | 8.28 |
| 16 AWG | 1.291 | 1.31 | 4.016 | 13.2 |
| 18 AWG | 1.024 | 0.823 | 6.385 | 20.9 |
| 20 AWG | 0.812 | 0.518 | 10.15 | 33.3 |
| 22 AWG | 0.644 | 0.326 | 16.14 | 52.9 |
| 24 AWG | 0.511 | 0.205 | 25.67 | 84.2 |
| 26 AWG | 0.405 | 0.129 | 40.81 | 134 |
| 28 AWG | 0.321 | 0.0810 | 64.90 | 213 |
| 30 AWG | 0.255 | 0.0509 | 103.2 | 339 |
How Temperature Changes Wire Resistance
In a metal, heat makes the lattice vibrate more, electrons scatter more often, and resistance goes up. The relationship is close to linear over normal working temperatures, which is what the coefficient α captures. Copper's α of 0.00393 per °C means +0.39% resistance for every degree above 20 °C:
| Conductor temperature | Copper resistance vs 20 °C | Typical situation |
|---|---|---|
| 0 °C | −7.9% | Outdoor winter run |
| 20 °C | reference | Bench / datasheet conditions |
| 40 °C | +7.9% | Warm loft or enclosure |
| 60 °C | +15.7% | Loaded cable, 60 °C insulation |
| 75 °C | +21.6% | THW / THWN rated terminal |
| 90 °C | +27.5% | THHN at full ampacity |
Alloys behave very differently. Constantan and manganin were designed to have an almost zero temperature coefficient, which is exactly why they are used for precision shunts and strain gauges — their resistance barely moves as they warm up.
Skin Effect: Why AC Resistance Is Higher
With alternating current, the changing magnetic field inside the conductor induces eddy currents that cancel the flow in the centre and reinforce it at the surface. The current ends up concentrated in a surface layer about one skin depth thick:
where \( f \) is the frequency in Hz, \( \mu_0 = 4\pi \times 10^{-7} \) H/m and \( \mu_r \) is the relative permeability of the conductor. This calculator then solves the exact Bessel-function expression for the AC-to-DC resistance ratio of a solid round wire (switching to the classic asymptotic form at very high frequency), so the figure stays accurate from mains frequency up into the RF range.
| Frequency | Skin depth in copper | Practical meaning |
|---|---|---|
| 50 Hz | 9.35 mm | Only large feeders and busbars are affected |
| 60 Hz | 8.53 mm | 4/0 copper gains about 0.5% resistance |
| 1 kHz | 2.09 mm | Audio and inverter harmonics start to matter |
| 100 kHz | 0.209 mm | 12 AWG shows roughly 2.7× its DC resistance |
| 1 MHz | 0.066 mm | RF work needs litz wire or tubing |
Note that ferromagnetic conductors such as steel and nickel have a relative permeability in the hundreds, so their skin depth is roughly \( \sqrt{\mu_r} \) times smaller — a steel wire's AC resistance climbs far faster than copper's.
Voltage Drop and Power Loss
Once you know the resistance of the run, the two numbers an installer actually cares about follow directly from Ohm's law:
The commonly quoted design targets, taken from the informational notes in the National Electrical Code, are 3% maximum drop on a branch circuit and 5% total including the feeder. Remember that the current flows out and back, so for a two-wire circuit you must use the round-trip length — which is why this calculator has a run-type selector rather than leaving you to double the number yourself.
What Affects Wire Resistance?
Resistance is directly proportional to length. Double the run and you double the resistance and the voltage drop.
Resistance is inversely proportional to area. Going up 3 AWG sizes doubles the area and halves the resistance.
Aluminium has about 1.6× the resistivity of copper; nichrome has about 64×, which is what makes it a heating element.
Metals gain roughly 0.4% resistance per °C. A hot conductor is a more resistive conductor, which then gets hotter still.
Skin effect pushes AC into the outer shell of the wire, raising the effective resistance above the DC value.
Stranded cable has slightly more resistance than solid wire of the same nominal size because the strands spiral and the packing is not perfect — typically 2-5%.
Worked Example
A 12 AWG copper cable feeds a 15 A load 50 ft away on a 120 V supply. The current runs out and back, so the conductor length is 100 ft (30.48 m). 12 AWG has a diameter of 2.053 mm, giving an area of 3.31 mm². At 20 °C:
\( R = \dfrac{1.724 \times 10^{-8} \times 30.48}{3.31 \times 10^{-6}} \approx 0.159\ \Omega \)
The voltage drop is \( 15 \times 0.159 \approx 2.38 \) V, which is 1.99% of 120 V — comfortably inside the 3% guideline — and the cable dissipates \( 15^{2} \times 0.159 \approx 35.8 \) W as heat. Warm the conductor to 60 °C and the resistance rises to about 0.184 Ω, pushing the drop to 2.30% and the loss to 41 W.
How to Use This Calculator
- Pick the conductor: Choose the material, then set the size by AWG gauge, by cross-sectional area (mm², kcmil or circular mils) or by diameter.
- Describe the run: Enter the wire length with its unit, choose one-way or round trip, and set how many conductors run in parallel.
- Set the temperature: Enter the operating temperature in °C or °F. Leave it at 20 °C for datasheet conditions.
- Add the load (optional): Enter the current, system voltage and AC frequency to get voltage drop, power loss and skin-effect resistance.
- Click Calculate Resistance: Read the resistance, the cross-section diagram, the temperature curve, the gauge comparison table and the step-by-step formulas.
Frequently Asked Questions
How do you calculate the resistance of a wire?
Wire resistance is R = ρ × L / A, where ρ is the resistivity of the conductor material in Ω·m, L is the conductor length in metres and A is the cross-sectional area in square metres. For a round wire the area is π × d² / 4. Because resistivity changes with temperature, ρ is first corrected with ρ_T = ρ₂₀ × [1 + α × (T − 20)].
What is the resistance of copper wire per foot?
At 20 °C, annealed copper has a resistivity of 1.724 × 10⁻⁸ Ω·m. That gives about 1.59 Ω per 1000 feet for 12 AWG, 2.53 Ω per 1000 feet for 14 AWG, 4.02 Ω per 1000 feet for 16 AWG and 6.39 Ω per 1000 feet for 18 AWG. Each three-gauge step roughly doubles the resistance.
Does wire resistance increase with temperature?
Yes, for metals. Copper has a temperature coefficient of about 0.00393 per °C, so its resistance rises about 0.39% for every degree above 20 °C. A copper conductor running at 75 °C has roughly 21% more resistance than the same conductor at 20 °C, which is why cable tables are published at a rated temperature.
Should I use one-way or round-trip length?
Use round trip whenever the current has to flow out and back through the same cable, which covers almost all DC, single-phase and low-voltage circuits. The current travels the length of the run twice, so the circuit resistance and the voltage drop are twice the one-way figure. Use one-way only when you want the resistance of a single conductor.
Why is AC resistance higher than DC resistance?
Alternating current pushes itself toward the outside of the conductor, an effect called skin effect. The current is concentrated within roughly one skin depth of the surface, so the effective cross-section shrinks and the resistance rises. At 60 Hz the skin depth in copper is about 8.5 mm, so only large conductors are affected, but at 1 MHz it is about 0.066 mm and even thin wire sees several times its DC resistance.
How much voltage drop is acceptable?
The widely used guideline, based on the informational notes in the National Electrical Code, is a maximum of 3% drop on a branch circuit and 5% total across feeder plus branch circuit. If your run exceeds those figures, use a larger conductor, shorten the run, split the load across parallel conductors or raise the system voltage.
Which wire material has the lowest resistance?
Silver has the lowest resistivity of any metal at 1.59 × 10⁻⁸ Ω·m, followed by copper at 1.724 × 10⁻⁸ and gold at 2.44 × 10⁻⁸. Copper is the practical choice because silver is expensive and gold conducts worse than copper. Aluminium has about 1.6 times the resistivity of copper but is roughly one third the weight, which is why it dominates overhead and large feeder cable.
Additional Resources
Citez ce contenu, cette page ou cet outil comme suit :
"Wire Resistance Calculator" sur https://MiniWebtool.com/fr/calculateur-de-resistance-de-fil/ de MiniWebtool, https://MiniWebtool.com/
by miniwebtool team. Updated: August 20, 2026
Outils d'Électronique:
- Calculateur d'autonomie de batterie En vedette
- Calculateur de Code Couleur de Résistance
- Calculatrice de la Loi d'Ohm
- Calculateur de chute de tension
- Calculateur de largeur de piste PCB
- Calculateur de Section de Fil Nouveau
- Calculateur de résistance pour LED Nouveau
- Calculateur de Diviseur de Tension Nouveau
- Calculateur de Résistances en Parallèle Nouveau
- Calculateur de condensateur Nouveau
- Calculateur de Minuteur 555 Nouveau
- Calculateur de Transformateur Nouveau
- Calculateur de Constante de Temps RC Nouveau
- Calculateur de Facteur de Puissance Nouveau
- Calculateur de Décibels (dB) Nouveau
- Calculateur d'impédance Nouveau
- Calculateur de fréquence de résonance Nouveau
- Simulateur de Portes Logiques Nouveau
- Calculateur de Résistances en Série Nouveau
- Calculateur de Watts en Ampères Nouveau
- Calculateur Ampères en Watts Nouveau
- Calculateur kVA Nouveau
- Calculateur de Puissance Triphasée Nouveau
- Convertisseur mAh en Wh Nouveau
- Calculateur de Taille de Générateur Nouveau
- Convertisseur Lumens en Watts Nouveau
- Calculateur de Lux en Lumens Nouveau
- Calculateur d'Éclairage de Pièce Nouveau
- Calculateur de Reactance Inductive Nouveau
- Calculateur de condensateurs en série et parallèle Nouveau
- Calculateur de Remplissage de Conduit Nouveau
- Calculateur de Longueur d'Antenne Nouveau