홈페이지 > 기타 도구 > 전자공학 도구 > Capacitor Bank Sizing Calculator
 

Capacitor Bank Sizing Calculator

Find the capacitor bank kVAR needed to correct your power factor to a target value. Enter kW, kVA, or measured volts and amps, and get the required kVAR, a matching standard capacitor bank built from real off-the-shelf steps, the per-phase capacitance in microfarads for both delta and wye connections, capacitor current with NEC 460.8 conductor and fuse sizing, released transformer capacity, and an animated power triangle showing the correction.

Capacitor Bank Sizing Calculator
Quick examples — click to fill the form, then press Calculate:
kW
V
Line-to-line voltage, e.g. 480, 415, 400 or 208
From the utility bill or meter. 0.75 or 75 both work.
0.95 is the usual utility threshold.

Embed Capacitor Bank Sizing Calculator Widget

Capacitor Bank Sizing Calculator 정보

The Capacitor Bank Sizing Calculator tells you exactly how many kVAR of power factor correction capacitors a load needs to move from its present power factor to a target such as 0.95. Enter the load as kW, as kVA, or as a clamp-meter reading in volts and amps, and the calculator returns the required kVAR, a bank you can actually buy built from standard capacitor ratings, the capacitance in microfarads for both delta and wye connections, the capacitor current with conductor and fuse sizing, and the transformer capacity the correction releases.

What is a capacitor bank and why size it?

Motors, transformers, welders and fluorescent ballasts are inductive: they draw a magnetising current that lags the voltage. That current does no useful work, but it still flows through every cable, breaker and transformer between the load and the utility. A capacitor bank installed near the load supplies that magnetising current locally, so the supply only has to deliver the real power. The result is a higher power factor, lower line current, less voltage drop, fewer losses, and — usually the reason the project gets funded — no more power factor penalty on the electricity bill.

Sizing matters in both directions. Too little kVAR and the penalty stays. Too much and the system overcorrects into a leading power factor at light load, which raises voltage, can upset generators and standby sets, and is penalised by many tariffs exactly like a lagging power factor.

Capacitor bank sizing formula

The whole calculation rests on one idea: capacitors change the reactive power \(Q\) and leave the real power \(P\) alone. The required kVAR is simply the difference between the reactive power you have and the reactive power you want.

Required capacitor kVAR
$$Q_C = P \times \left( \tan(\cos^{-1}\!PF_1) - \tan(\cos^{-1}\!PF_2) \right)$$
Real power from a kVA or ammeter reading
$$P = S \times PF_1 \qquad S_{3\phi} = \frac{\sqrt{3} \times V \times I}{1000} \qquad S_{1\phi} = \frac{V \times I}{1000}$$
Capacitance for a given kVAR
$$C_{\Delta} = \frac{Q_C / 3}{2\pi f V_{LL}^2} \qquad C_{Y} = 3 \times C_{\Delta} = \frac{Q_C}{2\pi f V_{LL}^2}$$

Where \(PF_1\) is the present power factor, \(PF_2\) the target, \(f\) the supply frequency in hertz, and \(V_{LL}\) the line-to-line voltage. The bracketed term is the familiar kVAR multiplier found in correction tables — it is what the table below lists.

Worked example

A 480 V three-phase plant draws 100 kW at a power factor of 0.75 and the utility wants 0.95. \(\tan(\cos^{-1}0.75) = 0.8819\) and \(\tan(\cos^{-1}0.95) = 0.3287\), so the multiplier is 0.5532 and the bank needs \(100 \times 0.5532 = 55.3\) kVAR. The nearest buildable bank is 60 kVAR (a 50 plus a 10), the apparent power falls from 133.3 kVA to 105.3 kVA, and the line current drops from 160 A to 127 A — 28 kVA of transformer capacity handed back without touching the transformer.

kVAR multiplier table

Multiply your load in kW by the factor where your present power factor meets your target.

Present PFTarget 0.90Target 0.95Target 0.98Target 1.00
0.600.8491.0051.1301.333
0.650.6850.8400.9661.169
0.700.5360.6920.8171.020
0.750.3980.5530.6790.882
0.800.2660.4210.5470.750
0.850.1350.2910.4170.620
0.900.1560.2810.484
0.920.0970.2230.426
0.950.1260.329

Notice how the last column grows. Going from 0.95 to 1.00 on a 100 kW load costs another 32.9 kVAR — about the same again as correcting 0.90 to 0.95 twice over. That is why almost nobody corrects to unity.

Delta or wye — which connection?

△ Delta (mesh)

Each cell sits across the full line-to-line voltage, so it produces three times the reactive power per microfarad. Needs the least capacitance and is the standard choice for low-voltage banks below 600 V. Every cell must be rated for the full line voltage.

Y Wye (star)

Each cell sees only \(V/\sqrt{3}\), so it needs three times the capacitance for the same kVAR but a lower voltage rating. Common at medium and high voltage, usually ungrounded, with the neutral used for unbalance and blown-fuse detection.

Fixed, switched or automatic?

Fixed bank

Always connected. Correct for a base load that never goes away — a transformer's magnetising kVAR, or a motor that runs continuously. Size it to the minimum load so it can never overcorrect.

Automatic bank

Several steps switched in and out by a power factor controller. The right answer whenever load varies through the shift or the total exceeds roughly 100 kVAR. Aim for 4 to 8 steps so correction tracks the load closely.

Detuned (reactor) bank

A series reactor tunes the bank below the 5th harmonic. Required wherever variable-speed drives, rectifiers or UPS systems make up a large share of the load, otherwise the capacitors and the harmonic source can resonate.

How to use this calculator

  1. Pick Three-Phase or Single-Phase and the supply frequency.
  2. Choose how you know the load: real power in kW, apparent power in kVA, or a measured current in amps at the system voltage.
  3. Enter the Current Power Factor — the value on the utility bill or the power meter. Both 0.78 and 78 are accepted.
  4. Enter the Target Power Factor. Use the threshold in your tariff, typically 0.90 or 0.95.
  5. Press Calculate kVAR, then use the target slider in the results to see how the bank size responds before you commit to a rating.

What power factor correction actually saves

  • Penalty removal. Tariffs charge either a power factor penalty below a threshold or a demand charge on kVA. Both disappear once the measured power factor sits above the target.
  • Released capacity. Apparent power falls from \(P/PF_1\) to \(P/PF_2\). That freed kVA is real headroom on the transformer, switchgear and feeders — often enough to add load without an upgrade.
  • Lower losses. Line current falls in the ratio \(PF_1/PF_2\), and resistive losses fall with the square of that ratio. Correcting 0.75 to 0.95 cuts current by about 21% and \(I^2R\) losses by about 38%.
  • Better voltage. Less current means less voltage drop along long feeders, which helps motors start and run cooler.

Common mistakes when sizing a capacitor bank

  • Sizing from peak kW but running at part load. A fixed bank sized for the busiest hour will overcorrect at night. Size fixed banks to the minimum load and switch the rest.
  • Ignoring harmonics. Capacitors are a low-impedance path for harmonic current. With significant drive or rectifier load, specify a detuned bank instead of plain capacitors.
  • Bolting too much kVAR onto a motor. Exceeding the manufacturer's maximum kVAR for terminal correction can self-excite the motor on coast-down and produce damaging overvoltage.
  • Undersized conductors and protection. NEC 460.8 wants at least 135% of rated capacitor current in the conductor; protection is normally set at 135–165%.
  • Forgetting discharge time. Capacitors store energy after the supply is opened. Codes require the residual voltage to fall to a safe level within a set time — never re-energise or work on a bank before the discharge resistors have done their job.

Frequently asked questions

How do I calculate the kVAR of a capacitor bank?

Multiply the real power in kW by the difference of the tangents of the two power factor angles: \(Q_C = kW \times (\tan\phi_1 - \tan\phi_2)\). A 100 kW load at 0.75 corrected to 0.95 needs \(100 \times (0.8819 - 0.3287) = 55.3\) kVAR.

What target power factor should I choose?

Match the threshold in your tariff. 0.95 is the common commercial target; 0.98 is worth it where the utility bills on kVA demand. Correcting to 1.00 is rarely economic and increases the risk of a leading power factor at light load.

How many microfarads is 1 kVAR?

It depends entirely on voltage and frequency, because \(C = Q / (2\pi f V^2)\). At 480 V and 60 Hz, one kVAR in a delta bank is roughly 3.8 µF per phase; at 240 V and 60 Hz the same kVAR needs about 15 µF, four times as much, because capacitance scales with the inverse square of voltage.

Can a capacitor bank be too large?

Yes. Overcorrection pushes the power factor leading, raises system voltage, can trip generator reverse-VAR protection and is often penalised by the utility. If the load varies, use an automatic bank with several switched steps rather than one large fixed block.

Does correcting power factor reduce my kWh consumption?

Only slightly. Capacitors do not reduce the real energy the load consumes; the meter's kWh register barely moves. The savings come from the removed penalty or kVA demand charge, the released capacity, and a modest cut in resistive losses in your own cables.

Where should the capacitors be installed?

The closer to the inductive load, the more of the distribution system is relieved. Individual correction at the motor gives the biggest loss reduction; group correction at a motor control centre is a good compromise; bulk correction at the main switchboard fixes the utility bill but leaves the internal cables carrying the same reactive current.

Disclaimer: this calculator provides guideline figures for planning and study purposes. Final capacitor bank design, harmonic analysis, protection settings and conductor sizing must be reviewed by a qualified electrical engineer against the applicable local code and the equipment manufacturer's data.

이 콘텐츠, 페이지 또는 도구를 다음과 같이 인용하세요:

"Capacitor Bank Sizing Calculator" - https://MiniWebtool.com/ko/콘덴서-뱅크-용량-계산기/에서 MiniWebtool 인용, https://MiniWebtool.com/

by miniwebtool team. Updated: 2026-08-19

전자공학 도구:

주요 도구:

인스타그램 사용자 ID 조회분수 계산기애너그램 생성기방어율 계산기내 행운의 숫자는?평균 계산기상대 표준 편차 계산기랜덤 이름 생성기👙 브라 사이즈 계산기파운드→킬로그램 변환기16진수에서 10진수로 변환기주사위 굴리기시험관 출산 예정일 계산기OPS 계산기🎮 게임 감도 변환기무작위 초능력 생성기러닝 페이스 계산기공백 제거16진수 변환기토크 변환기 (Nm, ft-lb, kgf-cm)kg에서 파운드로 변환기10진수를 16진수로 변환cm에서 피트와 인치로 변환기소인수분해 계산기사랑 궁합 계산기피트 인치 센티미터 변환기WAR 계산기무작위 토너먼트 대진표 생성기로마 숫자 변환기벤치 프레스 계산기요일 계산기💧 이슬점 계산기무작위 날짜 생성기이미지 분할기긴 나눗셈 계산기이닝당 적중률(WHIP) 계산기수면 계산기CAGR 계산기야구 배팅 계산기무작위 문자열 생성기FIP 계산기랜덤 영어 단어 생성기랜덤 생일 생성기줄 바꿈 제거랜덤 동물 생성기기대 수명 계산기명언 검색기 (영어)근무 시간 계산기YouTube 채널 통계랜덤 그룹 생성기월경주기 계산기ppm에서 퍼센트 변환기복리 계산기랜덤 토론 주제 생성기기울기 및 경사 계산기분수에서 소수로 계산기Watts to Amps CalculatorFPS 변환기연비 계산기면적 계산기자전거 사이즈 계산기속도 변환기mAh to Wh 변환기최대 공약수 계산기암페어에서 와트 계산기야구 장타율 계산기소수 검사기원형 면적 계산기📅 날짜 계산기금리 계산기분수 백분율 변환기비례식 계산기어린이 BMI 백분위수 계산기연봉 인상 계산기퍼센트에서 PPM으로 변환기잘고 텍스트 생성기주차 계산기변화율 계산기연중 일수 계산기 - 오늘은 올해의 몇 번째 날인가요HEX 계산기키 백분위수 계산기영업 마진 계산기바코드 생성기랜덤 식사 생성기타이어 크기 계산기형량 감경 계산기센티미터에서 인치로 변환기암호화폐 레버리지 계산기몫과 나머지 계산기인치에서 센티미터으로 변환기출루율 계산기작은 텍스트 생성기 ⁽ᶜᵒᵖʸ ⁿ ᵖᵃˢᵗᵉ⁾비디오 이미지 추출기출산 예정일 계산기⏱️ 시간 계산기혈당 변환기임신 날짜 계산기시저 암호 도구자동차 대출 계산기중앙값 계산기임대 수익률 계산기확률 계산기kVA 계산기PSI에서 bar로 변환기두 날짜 사이 일수 계산기출생 요일 계산기태양, 달 & 상승궁 계산기 🌞🌙✨kPa에서 psi로 변환기영업일 계산기거꾸로 텍스트 생성기모스 부호 생성기🎰 가챠 천장 계산기반지 사이즈 변환기십자수 실 계산기최대 심박수 계산기피타고라스 정리 계산기홈런 타율 계산기콜라츠 추측 계산기예쁜 글씨 생성기페이스북 사용자 ID 조회백분율 증가 계산기시간 지연 계산기임신 체중 증가 계산기간헐적 단식 계산기십진수에서 이진수로 변환기다중 분수 계산기랜덤 국가 생성기백분율 성장 계산기MAC 주소 조회단어 찾기 퍼즐 생성기일할 계산 월세 계산기번호 정렬16진수에서 이진법 변환기ANC 계산기오디오 추출기초과 근무 수당 계산기역함수 계산기영업 이익률 계산기암산 트레이너음력 양력 변환기YouTube 쇼츠 수익화 계산기🌬️ 체감 온도 계산기속도 계산기자녀 키 예측기퍼센트 감소 계산기헌혈 시간 계산기mcg에서 mg로 변환기마틴게일 전략 계산기반올림 계산기동영상 병합배당 수익률 계산기칵테일 ABV 계산기이진 계산기이진수를 십진수로 변환1RM (1회 최대 반복) 계산기TDEE 계산기목표 심박수 계산기볼링 점수 계산기임대료 인상 계산기자동차 감가상각 계산기직각삼각형 계산기태양 위치 계산기무작위 포커 핸드 생성기옥탄가 혼합 계산기정기 예금 계산기출석률 계산기텍스트 찾기 및 바꾸기호 길이 계산기랜덤 물품 생성기반전 텍스트HTML에서 텍스트 변환기공학용 계산기타원 둘레 계산기손절 및 익절 계산기취소선 텍스트 생성기가위바위보 생성기세제 사용량 계산기이름 번호 계산기n항 계산기백분율 할인 계산기소수 분수 변환기자전거 기어비 계산기급여 변환 계산기문자열 길이 얻기한 달에 일빗변 계산기스도쿠 생성기 및 풀이기즉시 연금 계산기랜덤 수학 문제 생성기미로 생성기색상 조합 생성기전선 게이지 계산기🖱️ 클릭 카운터SAT 점수 계산기낮잠 계산기변동 계수 계산기시간 지속 계산기신발 사이즈 변환기연분수 계산기중복 줄 제거게이머태그 생성기팀 이름 생성기닉네임 생성기랩 이름 생성기밴드 이름 생성기판타지 이름 생성기포춘 쿠키 생성기그림 아이디어 생성기저널 프롬프트 생성기데일리 확언 생성기칭찬 생성기작업 멘트 생성기아재 개그 생성기랜덤 농담 생성기랜덤 사실 생성기트리비아 문제 생성기행맨 단어 생성기픽셔너리 단어 생성기제스처 게임 생성기아이스브레이커 질문 생성기네버 해브 아이 에버 생성기밸런스 게임 생성기랜덤 질문 생성기AI 꿈 해몽AI 감사 편지 생성기AI 결혼식 축사 생성기AI 보도자료 생성기AI 제품 설명 생성기AI 영상 스크립트 생성기AI 유튜브 제목 및 설명 생성기AI 인스타그램 캡션 생성기AI LinkedIn 헤드라인 및 소개 생성기AI 이력서 불릿 생성기AI 커버레터 생성기AI 랩 가사 생성기PDF 평면화 도구PDF 잠금 해제 (소유자 암호 제거)PDF 텍스트 추출기PDF 페이지 추출기PDF 단어 세기PDF 보호PDF에 페이지 번호 추가PDF 페이지 순서 변경PDF 페이지 삭제PDF 회전JPG를 PDF로 변환PDF를 JPG로 변환PDF 압축PDF 분할PDF 병합PT에서 PX로 변환기PX에서 REM 변환기톨라에서 그램 변환기인도 토지 단위 변환기AI 노래 가사 생성기AI 시 생성기AI 스토리 생성기AI 번역기AI 텍스트 요약기mg에서 mL 변환기MPH에서 KMH 변환기노트-마일 변환기세제곱미터에서 세제곱피트세제곱피트에서 세제곱야드 변환기제곱피트에서 제곱미터 변환기제곱미터에서 제곱피트 변환기온스를 mL로 변환기mL를 온스로 변환기갤런에서 리터 변환기리터에서 갤런 변환기킬로그램 스톤 변환기스톤 킬로그램 변환기인치에서 밀리미터로 변환기밀리미터에서 인치로 변환기마일 킬로미터 변환기킬로미터-마일 변환기화씨-섭씨 변환기섭씨 화씨 변환기배낭 크기 계산기서핑보드 부피 계산기테니스 그립 사이즈 계산기헬멧 사이즈 계산기장갑 사이즈 계산기모자 사이즈 변환기스노보드 사이즈 계산기스키 사이즈 계산기스피드런 스플릿 타이머스테이블포드 계산기다트 체크아웃 계산기볼링 이코노미 계산기타격 스트라이크 레이트 계산기네트 런 레이트 계산기K/D 비율 계산기Elo 레이팅 계산기심박수 회복 계산기하이킹 시간 계산기로잉 페이스 계산기달리기 연령 등급 계산기FTP 및 파워 존 계산기Beep 테스트 계산기ACFT 점수 계산기Wilks & DOTS 계산기휠 오프셋 계산기타이어 하중 지수 및 속도 등급 조회마일당 비용 계산기리스 바이아웃 계산기2행정 오일 혼합 계산기엔진 배기량 계산기소파 문 통과 계산기장작 코드 계산기공기청정기 CADR 계산기제습기 크기 계산기천장 선풍기 크기 계산기커튼 크기 계산기러그 크기 계산기그림 거는 높이 계산기TV 설치 높이 계산기TV 크기 계산기연못 용적 및 라이너 계산기수영장 소금 계산기수영장 부피 계산기온수기 크기 계산기에폭시 레진 계산기난간동자 간격 계산기걸레받이 및 트림 계산기사이딩 계산기데크 스테인 계산기잔디 씨앗 계산기잔디 계산기아스팔트 계산기세제곱야드 계산기안테나 길이 계산기전선관 충전율 계산기직렬/병렬 커패시터 계산기유도 리액턴스 계산기방 조명 계산기럭스 루멘 계산기루멘 와트 변환기발전기 크기 계산기3상 전력 계산기직렬 저항 계산기마찰 계산기경사면 계산기기계적 이득 계산기음속 계산기파동 속도 계산기부력 계산기종단 속도 계산기드브로이 파장 계산기광자 에너지 계산기E=mc² 계산기케플러 제3법칙 계산기탈출 속도 계산기만유인력 계산기비어 람베르트 법칙 계산기네른스트 방정식 계산기삼투압 계산기끓는점 오름 계산기어는점 내림 계산기백분율 조성 계산기노르말 농도 계산기몰랄농도 계산기pKa Ka 변환기헨더슨 하셀바흐 계산기이론 수율 계산기한계 반응물 계산기전자 배치 계산기인터랙티브 주기율표AI 수업 지도안 생성기AI 퀴즈 생성기인용 생성기 (APA/MLA/Chicago)AP 점수 계산기ACT 점수 계산기유튜브 수익 추정기무작위 RPG 캐릭터 생성기